EVALUASI KELAYAKAN TAHANAN ISOLASI TRANSFORMATOR 30 MVA MENGGUNAKAN METODE INDEKS POLARISASI DAN TANGEN DELTA Transformer, Polarization Index, Tan Delta
Isi Artikel Utama
Abstrak
Use of a 30 MVA Auxiliary Transformer (UAT) Unit for a long period of time can experience insulation suitability problems, resulting in overvoltage and a decrease in insulation resistance. Humidity and high temperatures are factors that can cause mechanical damage which results in stopping the flow of electricity to the load. As a solution, the research carried out a feasibility test for the insulation resistance of a 30 MVA auxiliary transformer unit with a model determined as a transformer whose insulation feasibility was tested. The test uses the polarization index and tangent delta methods referring to the IEEE 43-2000 and ANSI C57.12.90 standards. The polarization index values obtained were 1.91 for HV-LV1+LV2+GND, 2.49 for LV1-HV+LV2+GND, and 1.87 for LV2-HV+LV1+GND. The tangent delta value in the 30 MVA Auxiliary Transformer Unit measurement is 0.323% for Primer ,0,949% for Secunder, and 0,834 for Tertier. These values indicate that the UAT isolation condition is still in good condition and suitable for operation.
##plugins.themes.bootstrap3.displayStats.downloads##
Rincian Artikel
Bagian
Referensi
“PT Cirebon Electric Power (CEP).”
[2] “B.P.Pemeliharaan, Buku pedoman pemeliharaan transformator tenaga,’ 2014.
[3] IEEE, “IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery IEEE Power and Energy Society,” The institute of Electrical and Electronics Engineers, Inc, vol. 43, pp. 9–14, 2000.
[4] C57.12.90-1999 Standard Test Code for Liquid-Immersed Distribution, Power and Regulating Transformers. IEEE, 1999.
[5] ade panji Nugraha, “Isolation Resistance Feasibility Test Analysis Based On Polarization Index And Delta Tangen In,” 2023.
[6] M. F. Robbani, D. Nugroho, and G. Gunawan, “Penentuan kelayakan tahanan isolasi pada transformator 60 MVA di gardu induk 150 KV tegal dengan menggunakan indeks polarisasi, tangen delta, dan breakdown Voltage,” Elektrika, vol. 12, no. 2, pp. 60–66, 2020.
[7] R. F. RIFQYAWAN, “¬ Analisis Uji Kelayakan Tahanan Isolasi Trafo 30 MVA di GI 150/20 KV PT APF Dengan Menggunakan Indeks Polarisasi Dan Tangen Delta,” 2022, Universitas Islam Sultan Agung.
[8] J. T. Elektro, F. Teknik, and U. Tidar, “Uji Kelayakan Belitan Unit Auxiliary Transformer ( UAT ) PLTU Rembang,” 2021.
[9] Nugroho R, “Analisis Kegagalan Auto Transfer Antara UAT (Unit Auxiliary Transformer) Dan SST (Station Service Transformer) Dikawasan GTG Indonesia Power Semarang,” pp. 40–46, 2021.
[10] IEC 60156 International Standard Norme Internationale Insulating liquids-Determination of the breakdown voltage at power frequency-Test method Isolants liquides-Détermination de la tension de claquage à fréquence industrielle-Méthode d’essai. 2018. [Online]. Available: www.iec.ch.
[11] Ir.Basuki Prayitno, Panduan Pemeliharaan trafo Tenaga. 2003.
[12] D. Sebagai and S. Satu, “Analisis Kualitas Tahanan Isolasi Pada Transformator Dengan Preventive Maintenance Di Gardu Induk Garuda Sakti Tugas Akhir.”